Description
1. The temperature measurement standard deviation is 0.2mK, and the long-term drift over a 24-hour period is less than 1 mK.
2. The temperature control stability is ±0.001°C.(which depends on the controlled object and parameters, meeting the stringent precision temperature control requirements for most applications, including those of semiconductor laser devices.)
3. Both bipolar and unipolar output modes are selectable options.
4. It allows for limiting the maximum rate of temperature change.
5. Supports the use of NTC (Negative Temperature Coefficient) thermistor temperature sensors.
6. Features a chip-scale design that facilitates integration into circuit board designs.
7. Incorporates an overheat protection function for the circuit board, ensuring reliable performance.
8. Offers a screen-display control module that allows direct parameter setting, with power-off memory for set data, making it convenient for production line workers.
9. Provides a complete set of serial communication control commands, offering an open platform for customization and interfacing.
10. Giving away computer software.
Instructional Video
SPECIFICATIONS(TEC103)
PARAMETERS |
MODEL |
UNIT |
|
TEC103L |
TEC103 |
||
24-hour Temperature Measurement Stability (with the matched thermistor) |
<0.001@20℃ |
<0.001@20℃ |
℃ |
Temperature drift caused by ambient temperature |
0.0001 |
0.0001 |
℃/℃ |
Optimal Temperature Control Stability (related to the overall system) |
±0.01 |
±0.001 |
°C |
Temperature Change Limit Setting Range |
0.1~10 |
0.1~10 |
℃/s |
Temperature Setting Method |
UART |
UART |
|
Power Supply Voltage (Short-term Maximum Voltage: 28V) |
7~24 |
7~24 |
V |
Output Polarity |
Bipolar、Unipolar |
Bipolar、Unipolar |
V |
Number of Temperature Control Zones |
1 |
1 |
|
Maximum Output Voltage |
±90%Vin (Settable) |
±90%Vin (Settable) |
|
Rated Current@24V |
±3 |
±3 |
A |
Ambient Temperature |
-55~60 |
-55~60 |
°C |
Ambient Humidity |
0-98 |
0-98 |
%RH |
Thermal Dissipation Requirements |
No Additional Thermal Dissipation Needed Within Rated Operating Range |
No Additional Thermal Dissipation Needed Within Rated Operating Range |
|
Circuit Board Overheat Protection |
Yes |
Yes |
|
Power Loss Memory |
Yes |
Yes |
|
PID Parameters |
User Adjustable |
User Adjustable |
|
Size |
46.5*39.0*9.6 |
46.5*39.0*9.6 |
mm³ |
Weight |
≈30 |
≈30 |
g |
Dimensional Drawing
。
Interfaces
Pin Number |
Pin Name |
Pin Type |
Pin Definition (High Level: 3.3V, Low Level: 0V) |
1 |
GND |
Input |
Power Input Negative Pole (Low Current). |
2 |
STATE |
Output |
Temperature Control Status Output. High Level: Temperature control is functioning normally (temperature control error < 0.01°C). Low Level: Temperature control anomaly detected (temperature control error ≥ 0.01°C). The temperature control standard of 0.01°C can be set. |
3 |
ENABLE |
Input |
Output Enable Pin. High Level (Default): Enables temperature control output. Low Level: Disables temperature control output. |
4 |
TX2 |
Output |
Serial Port 2 Receiver, TTL Level, used for connecting to the Screen Display Control Module. |
5 |
RX2 |
Input |
Serial Port 2 Receiver, TTL Level, used for connecting to the Screen Display Control Module. |
6 |
VCC |
Output |
3.3V Output, intended for connection to the screen display control module and not recommended for other uses. |
7 |
TX1 |
Output |
Serial Port 1 Receive End, TTL level, used for connecting to PC control software. Data bits: 8 bits, Stop bits: 1 bit, Parity: None, Baud Rate: 38400. |
8 |
RX1 |
Input |
Serial Port 1 Receive End, TTL level, used for connecting to PC control software. Data bits: 8 bits, Stop bits: 1 bit, Parity: None, Baud Rate: 38400. |
9 |
NTC- |
Input |
Thermistor (NTC) Interface, compatible with different resistance values of NTC thermistors, with wiring polarity not required. |
10 |
NTC+ |
Input |
Thermistor (NTC) Interface, compatible with different resistance values of NTC thermistors, with wiring polarity not required. |
11 |
GND |
Input |
Power Input Negative Pole (High Current). |
12 |
GND |
Input |
Power Input Negative Pole (High Current). |
13 |
Vin |
Input |
Power Input Positive Pole, with an input voltage range of 7 to 24V. |
14 |
Vin |
Input |
Power Input Positive Pole, with an input voltage range of 7 to 24V. |
15 |
TEC- |
Output |
The negative terminal of the temperature control current output is usually connected to the negative terminal of the Thermoelectric Cooler (TEC). |
16 |
TEC- |
Output |
The negative terminal of the temperature control current output is usually connected to the negative terminal of the Thermoelectric Cooler (TEC). |
17 |
TEC+ |
Output |
The positive terminal of the temperature control current output is typically connected to the positive terminal of the Thermoelectric Cooler (TEC). |
18 |
TEC+ |
Output |
The positive terminal of the temperature control current output is typically connected to the positive terminal of the Thermoelectric Cooler (TEC). |
。
Evaluation Board
SELECTION GUIDE
MODEL |
STABILITY (℃)@20℃ |
SUPPORTED SENSOR TYPES |
CHANNELS |
DRIVING CAPACITY @24V |
POWER SUPPLY VOLTAGE(V) |
DIMENSION (mm) |
FEATURES |
±0.01 |
NTC |
1 |
±3A |
7-24 |
46.5*39.0*14.8 |
Small-sized |
|
±0.001 |
|||||||
±0.01 |
NTC PT1000 |
2 |
±7A |
94.3*79.5*20.5 |
Capable of driving solid-state relays and thyristors |
||
±0.001 |
|||||||
±0.01 |
±15A |
||||||
±0.001 |
|||||||
±0.001 |
NTC PT1000 CCR Low Temperature Resistor |
Capable of driving solid-state relays and thyristors with resistor temperature calibration function |